Designed primarily for single outlet use. It delivers safe, blended hot water
to taps, showers, bidets and other water outlets, making it ideal for use in
prisons, police, hospitals, and schools. It has been specifically designed and
manufactured to meet the general requirements of: National Health Service Model
Engineering Specification - Thermostatic Mixing Valves - Heath Premises - DO8
and BS 7942: 2000 Thermostatic Mixing Valve for use in care establishments
(TMV3) BS EN 1111 : 1999 Sanitary tapware. Thermostatic Mixing Valves (PN10)
General Technical specification & BS EN 1287: 1999 Sanitary tapware. Low
Pressure Thermostatic Mixing Valves General technical specification (TMV2) It
has been independently tested and approved by the TMV3 scheme as a type 3 valve
under the requirements of the NHS MES - DO8 and approved by Buildcert as meeting
the requirements of the TMV2 scheme The element that controls the temperature of
the mixed water discharging from the valve works proportionally on both hot and
cold water supplies in order to maintain the temperature of the mixed after
discharged.
specification
- Robust and Reliable
- Highly Resistant to Scaling
- Anti Tamper Proof Head
- WRAs Approved
- One Valve Suits All Applications
- Cartridge Construction
- High Flow Rate
- Low Pressure Drop
technical data
- Temperature Adjustment Range 30°C to 50°C
- Temperature Stability ±2°C
- Maximum Inlet Temperature 85°C
- Maximum Working Pressure 10 Bar : Static
- Minimum Working Pressure 0.2 Bar : Dynamic
- Inlet Temperature Range 52°C - 65°C : Hot Supply
- 05°C - 20°C : Cold Supply
- D08 Working Pressure Ranges 0.2 - 1.0 : Low Pressure
- 1.0 - 5.0 : High Pressure
- Max. Temp. Differential (Mix to Hot)
- for fail safe 10°C
- Maximum Pressure Inlet differential 5:1
finish options
|